Centrifugal Roof Fans - RBH

This product range is now obsolete and no longer available from Vent-Axia. The information here is provided for reference only.

At a Glance:

Motors protected to IP44
Motor insulation Class ‘B’
Maximum operating temperature 40˚C
Standard Thermal Overload Protection
IP65 service isolator, except on size 250 dia where a service switch is provided
Bird guard
Speed controllable motors
Manufacture controlled to BS EN ISO9001
Performance tested to BS 848 Part 1 & 2
2 Year Guarantee
 

Specially designed for use when high pressure characteristics are required. Centrifugal roof models are delivered on-site ready for installation, fully assembled including service isolator. The range consists of 9 sizes with duties from 0.248m 3/s to 4.5m3 /s(892m3 /h to 16200m3 /h) with high pressure development available up to 900 Pa making this range particularly suited for ducted applications.

The mounting plate is moulded with an integral fixed bellmouth to ensure optimum efficiency and precise alignment. The weather-cowl is also moulded to produce a smooth internal surface and a tough UV resistant finish. Colour: BS 10A07. Alternative colours available on request. Equally suitable for flat or inclined roofs, backward curve centrifugal roof models are suitable for kerb or purlin box mounting and feature a wide range of accessories for many different industrial applications.

Vent-Axia centrifugal roof fans are designed for either kerb or inclined fixing (max. angle 30°).

Motors

The Centrifugal roof range features a proven external rotor motor and backward curved aluminium impeller assembly selected for performance and non-overloading characteristics. The assembly is dynamically balanced to VDI 2060. The motors in this range are protected to IP44 according to BS EN 60529. Ball bearings are greased for life and are designed to run at any angle. Insulation is Class 'B' (from -30°C to +40°C). Manufacture is controlled to BS EN ISO 9001 standards.

Electrical

Single phase 220-240V Hz. Capacitor start and run. Three phase 380-415V 50Hz. A service isolator switch is provided for local isolation to meet COSHH requirements. The enclosure is protected to IP65 according to BS EN 60529, except on size 250 dia where a service switch is provided.

All motors are fitted with Standard Thermal Overload Protection (S.T.O.P), which for three phase fans should be wired into all controller circuits and into starter contactors. Most models are available with 4, 6 and 8 pole motors.

Sound Levels
Published dB(A) figures are free field sound pressure levels at 3m with spherical propagation at a reference level of 2 x 10–5Pa (20 micro-Pascals).

The sound power levels spectra figures are dB with a reference level of 10–12 Watts (1 pico watt).

Centrifugal Roof Fan Accessories

Purlin boxes
Available in sizes to suit all models. Should be used to support the fan in conjunction with a soaker flange sheet.

Roof attenuators
Available in all sizes to cover the range of centrifugal roof fans in three lengths: 600, 900 or 1200mm according to the attenuation required.

Shutters
Robust construction and designed to fit beneath the fan using the fittings provided. Airflow operated, manual or motorisable shutter. A minimum distance of half the attenuator width is required between an airflow shutter and a roof attenuator for satisfactory operation.

DIMENSIONS:

Fan Size a b c d Weight Kg
250 500 500 280 90 16
315/355 700 680 410 83 16/22
400/450 800 780 480 83 24/27
500/560 950 930 575 103 35/46
630/710 1230 1055 630 103 57/73
 

 

Raadpleeg de tab Downloads voor technische informatie

 

 

ESTIMATED RUNNING COSTS

Calculate estimated running costs for this product using the tool below.
For average costs*, leave the default values in place or enter your own figures in the boxes to recalculate.
Where a product has multi speeds, a typical installation has been used for the below calculations. *Running cost does not include the use of the heater on the heater model


pence
(Your current electricity cost in pence per hour. This will be listed on your electric bill)
hours
(The average number of hours per day fan to run in Trickle mode)
hours
(The average number of hours per day fan to run in Boost mode)

Based on the inputted figures, estimated running costs would be:

Overview

Specially designed for use when high pressure characteristics are required. Centrifugal roof models are delivered on-site ready for installation, fully assembled including service isolator. The range consists of 9 sizes with duties from 0.248m 3/s to 4.5m3 /s(892m3 /h to 16200m3 /h) with high pressure development available up to 900 Pa making this range particularly suited for ducted applications.

The mounting plate is moulded with an integral fixed bellmouth to ensure optimum efficiency and precise alignment. The weather-cowl is also moulded to produce a smooth internal surface and a tough UV resistant finish. Colour: BS 10A07. Alternative colours available on request. Equally suitable for flat or inclined roofs, backward curve centrifugal roof models are suitable for kerb or purlin box mounting and feature a wide range of accessories for many different industrial applications.

Vent-Axia centrifugal roof fans are designed for either kerb or inclined fixing (max. angle 30°).

Motors

The Centrifugal roof range features a proven external rotor motor and backward curved aluminium impeller assembly selected for performance and non-overloading characteristics. The assembly is dynamically balanced to VDI 2060. The motors in this range are protected to IP44 according to BS EN 60529. Ball bearings are greased for life and are designed to run at any angle. Insulation is Class 'B' (from -30°C to +40°C). Manufacture is controlled to BS EN ISO 9001 standards.

Electrical

Single phase 220-240V Hz. Capacitor start and run. Three phase 380-415V 50Hz. A service isolator switch is provided for local isolation to meet COSHH requirements. The enclosure is protected to IP65 according to BS EN 60529, except on size 250 dia where a service switch is provided.

All motors are fitted with Standard Thermal Overload Protection (S.T.O.P), which for three phase fans should be wired into all controller circuits and into starter contactors. Most models are available with 4, 6 and 8 pole motors.

Sound Levels
Published dB(A) figures are free field sound pressure levels at 3m with spherical propagation at a reference level of 2 x 10–5Pa (20 micro-Pascals).

The sound power levels spectra figures are dB with a reference level of 10–12 Watts (1 pico watt).

Centrifugal Roof Fan Accessories

Purlin boxes
Available in sizes to suit all models. Should be used to support the fan in conjunction with a soaker flange sheet.

Roof attenuators
Available in all sizes to cover the range of centrifugal roof fans in three lengths: 600, 900 or 1200mm according to the attenuation required.

Shutters
Robust construction and designed to fit beneath the fan using the fittings provided. Airflow operated, manual or motorisable shutter. A minimum distance of half the attenuator width is required between an airflow shutter and a roof attenuator for satisfactory operation.

Technical

DIMENSIONS:

Fan Size a b c d Weight Kg
250 500 500 280 90 16
315/355 700 680 410 83 16/22
400/450 800 780 480 83 24/27
500/560 950 930 575 103 35/46
630/710 1230 1055 630 103 57/73
 

Downloads